Flight Systems
Generator Controls spacer Engine Idle Limiter spacer About Us
RV Controls Highway, Marine & Industrial Controls


REPRESENTATIVES WANTED
Click here for more info



Industrial Controls

Model 565 Engine Saver® - with Gauges

Factory Direct: $2,795

View the Product Manual
Click Here to View Model 565 Internal Layout


img
img

Engine Start/Stop Controller / Engine Saver® with Gauges

The Model 565 provides a complete Engine Compartment Gauge Package combined with the proven protection of the Engine Saver®. It features a switch which allows the Engine to be operated locally, or from a typical remote location, such as a control room or, in Marine applications, a vessel's bridge.

See What the Engine Saver has Done:
Finsch Mine – Komatsu 680 Dump Truck powered by Cummins KT 1710 engine. The Engine Saver shut down on low oil pressure. Found blocked oil filter and diesel fuel in engine oil. Read more...

The Engine Saver® monitors a combination of pressure, temperature and RPM on 8, 12 and 16 cylinder diesel or gas engines, and detects the early signs of trouble before damage occurs - long before an attentive operator could detect it on the gauges - and without false alarms. Most common faults go undetected until they cause consequential damage or engine destruction.


$300 Allowance for your old protection system when you Upgrade to the 565 Engine Saver®/Gauge Package! Click here for details

The Engine Saver® Detects

  • Loss of coolant
  • Low coolant
  • De-aeration baffle fatigue
  • Broken/worn rings
  • Hole in a piston
  • Loss of oil
  • Partially blocked oil or water pumps
  • Fuel dilution
  • Overspeed
  • Overheating
  • Clogged breathers
  • Worn pump impellers
  • Worn bearings
  • Governor failure
  • Radiator cap loose
  • Scored cylinder

Guage Layout

  • Engine Coolant Temp: 100-250°F(40-120°C)
  • Oil Pressure: 0-80 PSI(0-500 kPA)
  • Oil Temperature: 140-300° F(60-150°C)
  • System Voltages: 16-36 VDC
  • Tach: 0-3000 RPM with Digital Hour Meter
  • Dual Pyrometer EGT +/intercooler or left & right manifolds 0 - 1600° f

Controls on Unit

  • Key operated 3 position switch– Off, Ignition, Start (spring back)
  • Two keys supplied
  • Backlit gauges with on-off option

The engine is protected over its entire operating range from idle to peak torque to maximum allowable RPM. The unit is fully adjustable to suit all types of engines in all types of operating conditions

  • Mining
  • Construction
  • Irrigation
  • Marine
  • Railway
  • Military
  • Power Generation

Features:

  • Built-in status panel (Optional remote available) gives complete engine operating condition and fault location, even after shutdown
  • Auxiliary analog outputs for trend analysis and overhaul/maintenance forecasting via radio data link and/or on-board recording
  • SPDT heavy-duty output relay permits a wide choice of alarm/shutdown options including pre-shutdown warning
  • Trip points automatically lower when engine is idling or lugged down. All trip and enable points are fully adjustable. Enable time delay changes automatically with engine temperature
  • Unit will enable on Turbo Boost or RPM (or both) at installer's option. Choice of 3 RPM sources
  • All internal adjustments have status indicator and are marked for accurate and easy adjustment
  • Two custom optional inputs
  • Failsafe operation with flashing lights showing location
  • Easy to install - complete manual supplied
  • Weather resistant and tamper proof; unit is lockable
  • 24V input - transient and reverse polarity protected, suppressors built-in to withstand nearby arc welding
  • Fully supported with spare parts, repair service and test equipment
Parameter Adjustment Range Factory Setting
TURBO ENABLE NON-ADJUSTABLE 8 PSI
RPM ENABLE 300-1800 RPM 500 RPM
OVERSPEED 1800-3000 RPM 2500 RPM
CRANKCASE PRESSURE FIXED 8", 10" or 15" 10" H2O
IDLE OIL PRESSURE 5-15 PSI MODULATED 12 PSI
RUN OIL PRESSURE 25-50 PSI MODULATED 42 PSI
IDLE COOLANT PRESSURE 0-9 PSI MODULATED 3 PSI
RUN COOLANT PRESSURE 5-30 PSI MODULATED 15 PSI
TEMPERATURE 65-140° C 100° C
SHUTDOWN DELAY 1-60 SECONDS 20 SECONDS

Stop Destroying Engines - Use the Engine Saver®

remote-digital-redout-display

Recommended Remote Digital Readout - P/N 57-A550-41

This is the perfect accessory for the Model 565 – it plugs right into the harness connector on the unit (20' max) and provides switch selectable accurate digital readout of all monitored parameters. Also included are protection enabled and alarm lights plus an audible alarm and test switch.

Factory Direct: $436

Contact Installing Distributor

Reconditioning Service Available for older Model 565 Engine Savers; Click here for details